<img height="1" width="1" style="display:none;" alt="" src="https://analytics.twitter.com/i/adsct?txn_id=nxxi1&amp;p_id=Twitter&amp;tw_sale_amount=0&amp;tw_order_quantity=0"> <img height="1" width="1" style="display:none;" alt="" src="//t.co/i/adsct?txn_id=nxxi1&amp;p_id=Twitter&amp;tw_sale_amount=0&amp;tw_order_quantity=0">

Our Products

Facility Design and Specification

Space

  • Dedicated, purpose-built, slab-on-grade construction with insulated pre-cast concrete panel construction
  • Phase 1 building with over 12,000 ft2 of total area
  • Approx. 7500 ft2 colocation space with anti-static flooring
  • Phase 2 footprint provides additional 10,000 ft2 of colocation space
  • On-site expansion to support up to 32,000 ft2 of total area
  • Secure loading bay to support shipping and receiving

Power

  • 100% guaranteed power availability 
  • 2.5 MW dedicated feed from the city of Lethbridge expandable to 5 MW 
  • Phase 1 power generator 1.5 MW
  • Building and site ready for second generator
  • 2x Double conversion online APC Symmetra MW, 800 KW each, 2(N + 1) redundant 
  • A+B power paths to all customer infrastructure from independent UPS 
  • Continuous duty-rated generator, maintained weekly
  • 20 minutes UPS runtime at full load  
  • Refueling contracts to ensure uptime 

Cooling

  • Chilled glycol system
  • 2x 160 ton Daiken/McQuay chillers
  • 2x dry coolers (lowers operational costs)
  • Redundant and fault tolerant cooling design 
  • Humidity controlled facility 

Fire Protection

  • Multi-stage, cross-zoned configuration
  • Smoke and heat sensors as well as VESDATM
  • 3M NOVECTM 1230 Sapphire clean agent

Security

  • Multi-zone, 2 factor authentication on all exterior entrances
  • All access logged and auditable
  • Customer access cards are authorized for time on-site only
  • Extensive network of video surveillance 
  • IP camera system
  • Long term (off-site) retention
  • Fully fenced and monitored mechanical yard 
  • Centralized Security Coordination Centre 
  • 24x7 unescorted access privileges for customers

Connectivity

  • 3 diverse fibre paths into our facility 
  • On-net with Shaw, TELUS, and Cybera
  • Axia connectivity available
  • Meet-Me room with Single-mode (SM) / Multi-mode (MM) / copper connectivity
  • Carrier-grade Juniper switching and routing infrastructure 
  • Multi-homed BGP internet services available
  • Upstream providers include TELUS, Hurricane Electric, Cogent, GTT